15KV ACSR TREE WIRE (2 layer)
|
Size (AWG or kcmil) |
Stranding |
Conductor |
Covering Thickness (mils) |
Cable O.D. |
Rated Strength |
Weight per 1000ft |
|
|
Diameter |
|||||||
|
(mils) |
Inner Layer |
Outer Layer |
(mils) |
(lbs) |
(lbs) |
||
|
4 |
6/1 |
250 |
75 |
75 |
550 |
1767 |
136 |
|
2 |
6/1 |
316 |
75 |
75 |
616 |
2708 |
184 |
|
1/0 |
6/1 |
398 |
75 |
75 |
698 |
4161 |
255 |
|
2/0 |
6/1 |
447 |
75 |
75 |
747 |
5045 |
303 |
|
3/0 |
6/1 |
502 |
75 |
75 |
802 |
6289 |
362 |
|
4/0 |
6/1 |
563 |
75 |
75 |
863 |
7933 |
432 |
|
266.8 |
18/1 |
609 |
75 |
75 |
909 |
6536 |
441 |
|
266.8 |
26/7 |
642 |
75 |
75 |
942 |
10735 |
452 |
|
336.4 |
18/1 |
684 |
75 |
75 |
984 |
8246 |
536 |
|
336.4 |
26/7 |
720 |
75 |
75 |
1020 |
13395 |
555 |
|
336.4 |
30/7 |
741 |
75 |
75 |
1041 |
16435 |
621 |
|
397.5 |
18/1 |
743 |
75 |
75 |
1043 |
9443 |
611 |
|
397.5 |
24/7 |
772 |
75 |
75 |
1072 |
13870 |
609 |
|
397.5 |
26/7 |
783 |
75 |
75 |
1083 |
1545 |
645 |
|
477 |
24/7 |
846 |
75 |
75 |
1146 |
16340 |
719 |
|
477 |
26/7 |
858 |
75 |
75 |
1158 |
18525 |
762 |
|
477 |
30/7 |
883 |
75 |
75 |
1183 |
22610 |
854 |
|
556.5 |
18/1 |
879 |
75 |
75 |
1179 |
13015 |
813 |
|
556.5 |
24/7 |
914 |
75 |
75 |
1214 |
18810 |
828 |
|
556.5 |
26/7 |
927 |
75 |
75 |
1227 |
21470 |
878 |
|
636 |
18/1 |
940 |
75 |
75 |
1240 |
14915 |
912 |
|
636 |
24/7 |
977 |
75 |
75 |
1277 |
20900 |
936 |
|
636 |
26/7 |
990 |
75 |
75 |
1290 |
23940 |
993 |
|
795 |
26/7 |
1108 |
80 |
75 |
1428 |
29925 |
1234 |
|
795 |
45/7 |
1063 |
80 |
80 |
1383 |
20995 |
1031 |
15kV Tree Wire (3 layer)
|
15kV Tree Wire ANSI/ICEA S-121-733 |
|||||||
|
Size |
No. |
Covering Thickness |
Cable Diameter |
Rated |
Weight |
||
|
Conductor Shield |
Inner Layer |
Outer Layer |
|||||
|
No. |
mm |
mm |
mm |
mm |
kN |
kg/km |
|
|
3-Layer 15kV ACSR/XLPE/HDPE |
|||||||
|
6 |
6/1 |
0.38 |
1.91 |
1.91 |
13.6 |
5.28 |
188 |
|
4 |
6/1 |
0.38 |
1.91 |
1.91 |
14.8 |
8.30 |
238 |
|
3 |
6/1 |
0.38 |
1.91 |
1.91 |
15.6 |
10.20 |
271 |
|
2 |
6/1 |
0.38 |
1.91 |
1.91 |
16.5 |
12.70 |
313 |
|
1 |
6/1 |
0.38 |
1.91 |
1.91 |
17.4 |
15.60 |
362 |
|
1/0 |
6/1 |
0.38 |
1.91 |
1.91 |
18.5 |
19.40 |
424 |
|
2/0 |
6/1 |
0.38 |
1.91 |
1.91 |
19.6 |
23.30 |
496 |
|
3/0 |
6/1 |
0.38 |
1.91 |
1.91 |
20.7 |
29.40 |
584 |
|
4/0 |
6/1 |
0.38 |
1.91 |
1.91 |
22.4 |
37.10 |
699 |
|
266.8 |
18/1 |
0.38 |
1.91 |
1.91 |
23.7 |
30.30 |
713 |
|
336.4 |
18/1 |
0.38 |
1.91 |
1.91 |
25.2 |
38.20 |
847 |
|
3-Layer 15kV AAAC/XLPE/HDPE |
|||||||
|
48.69 |
7 |
0.38 |
1.91 |
1.91 |
15.2 |
7.83 |
223 |
|
77.47 |
7 |
0.38 |
1.91 |
1.91 |
16.8 |
12.4 |
286 |
|
123.3 |
7 |
0.38 |
1.91 |
1.91 |
19.0 |
18.9 |
383 |
|
155.4 |
7 |
0.38 |
1.91 |
1.91 |
20.1 |
23.8 |
443 |
|
195.7 |
7 |
0.38 |
1.91 |
1.91 |
21.5 |
30.0 |
521 |
|
246.9 |
7 |
0.38 |
1.91 |
1.91 |
23.0 |
37.8 |
614 |
|
312.8 |
19 |
0.38 |
1.91 |
1.91 |
24.9 |
46.5 |
740 |
|
394.5 |
19 |
0.38 |
1.91 |
1.91 |
27.4 |
58.6 |
892 |
|
465.4 |
19 |
0.38 |
1.91 |
1.91 |
28.4 |
69.2 |
1008 |
|
559.5 |
19 |
0.51 |
1.91 |
1.91 |
30.4 |
83.1 |
1168 |
|
652.4 |
19 |
0.51 |
1.91 |
1.91 |
31.8 |
97.0 |
1320 |
|
740.8 |
37 |
0.51 |
1.91 |
1.91 |
33.3 |
107 |
1463 |
|
3-Layer 15kV AAC/XLPE/HDPE |
|||||||
|
4 |
7 |
0.38 |
1.91 |
1.91 |
14.4 |
3.52 |
204 |
|
2 |
7 |
0.38 |
1.91 |
1.91 |
15.8 |
5.39 |
259 |
|
1/0 |
7 |
0.38 |
1.91 |
1.91 |
17.7 |
7.96 |
341 |
|
2/0 |
7 |
0.38 |
1.91 |
1.91 |
18.6 |
9.99 |
394 |
|
3/0 |
7 |
0.38 |
1.91 |
1.91 |
19.7 |
12.15 |
459 |
|
4/0 |
7 |
0.38 |
1.91 |
1.91 |
21.1 |
15.30 |
541 |
|
266.8 |
19 |
0.38 |
1.91 |
1.91 |
23.0 |
19.89 |
648 |
|
336.4 |
19 |
0.38 |
1.91 |
1.91 |
24.9 |
24.57 |
775 |
|
397.5 |
19 |
0.38 |
1.91 |
1.91 |
26.1 |
28.44 |
878 |
|
477 |
19 |
0.38 |
1.91 |
1.91 |
27.9 |
33.30 |
1017 |
|
556.5 |
37 |
0.51 |
1.91 |
1.91 |
30.1 |
39.87 |
1161 |
|
636 |
37 |
0.51 |
1.91 |
1.91 |
31.5 |
45.36 |
1295 |
|
795 |
37 |
0.51 |
2.03 |
2.03 |
34.2 |
55.62 |
1557 |
25kV Tree Wire (3 layer)
|
25kV Tree Wire ANSI/ICEA S-121-733 |
|||||||
|
Size |
No. |
Covering Thickness |
Cable diameter |
Rated |
Weight |
||
|
Conductor Shield |
Inner Layer |
Outer Layer |
|||||
|
No. |
mm |
mm |
mm |
mm |
kN |
kg/km |
|
|
3-Layer 25kV ACSR/XLPE/HDPE |
|||||||
|
1/0 |
6/1 |
0.38 |
3.18 |
3.18 |
23.6 |
19.4 |
586 |
|
2/0 |
6/1 |
0.38 |
3.18 |
3.18 |
24.7 |
23.3 |
666 |
|
3/0 |
6/1 |
0.38 |
3.18 |
3.18 |
25.8 |
29.4 |
763 |
|
4/0 |
6/1 |
0.38 |
3.18 |
3.18 |
27.5 |
37.1 |
891 |
|
266.8 |
18/1 |
0.38 |
3.18 |
3.18 |
28.6 |
30.3 |
913 |
|
336.4 |
18/1 |
0.38 |
3.18 |
3.18 |
30.1 |
38.2 |
1058 |
|
3-Layer 25kV AAAC/XLPE/HDPE |
|||||||
|
48.69 |
7 |
0.38 |
3.18 |
3.18 |
20.1 |
7.83 |
358 |
|
77.47 |
7 |
0.38 |
3.18 |
3.18 |
21.7 |
12.4 |
434 |
|
123.3 |
7 |
0.38 |
3.18 |
3.18 |
23.9 |
18.9 |
547 |
|
155.4 |
7 |
0.38 |
3.18 |
3.18 |
25.0 |
23.8 |
616 |
|
195.7 |
7 |
0.38 |
3.18 |
3.18 |
26.4 |
30.0 |
704 |
|
246.9 |
7 |
0.38 |
3.18 |
3.18 |
27.9 |
37.8 |
809 |
|
312.8 |
19 |
0.38 |
3.18 |
3.18 |
29.6 |
46.5 |
939 |
|
394.5 |
19 |
0.38 |
3.18 |
3.18 |
32.1 |
58.6 |
1109 |
|
465.4 |
19 |
0.38 |
3.18 |
3.18 |
33.1 |
69.2 |
1232 |
|
559.5 |
19 |
0.51 |
3.18 |
3.18 |
35.1 |
83.1 |
1407 |
|
652.4 |
19 |
0.51 |
3.18 |
3.18 |
36.5 |
97.0 |
1569 |
|
740.8 |
37 |
0.51 |
3.18 |
3.18 |
38.0 |
107 |
1723 |
|
927.2 |
37 |
0.51 |
3.18 |
3.18 |
40.9 |
135 |
2050 |
|
3-Layer 25kV AAC/XLPE/HDPE |
|||||||
|
1/0 |
7 |
0.38 |
3.18 |
3.18 |
22.8 |
7.96 |
497 |
|
2/0 |
7 |
0.38 |
3.18 |
3.18 |
23.7 |
9.99 |
556 |
|
3/0 |
7 |
0.38 |
3.18 |
3.18 |
24.8 |
12.15 |
630 |
|
4/0 |
7 |
0.38 |
3.18 |
3.18 |
26.2 |
15.30 |
723 |
|
266.8 |
19 |
0.38 |
3.18 |
3.18 |
27.7 |
19.89 |
833 |
|
336.4 |
19 |
0.38 |
3.18 |
3.18 |
29.6 |
24.57 |
973 |
|
397.5 |
19 |
0.38 |
3.18 |
3.18 |
30.8 |
28.44 |
1086 |
|
477 |
19 |
0.38 |
3.18 |
3.18 |
32.6 |
33.30 |
1237 |
|
556.5 |
37 |
0.51 |
3.18 |
3.18 |
34.8 |
39.87 |
1398 |
|
636 |
37 |
0.51 |
3.18 |
3.18 |
36.2 |
45.36 |
1542 |
|
795 |
37 |
0.51 |
3.18 |
3.18 |
38.9 |
55.62 |
1824 |
35kV Tree Wire (3 layer)
|
35kV Tree Wire ANSI/ICEA S-121-733 |
|||||||
|
Size |
No. |
Covering Thickness |
Cable Diameter |
Rated |
Weight |
||
|
Conductor Shield |
Inner Layer |
Outer Layer |
|||||
|
No. |
mm |
mm |
mm |
mm |
kN |
kg/km |
|
|
3-Layer 35kV ACSR/XLPE/HDPE |
|||||||
|
1/0 |
6/1 |
0.38 |
4.45 |
3.18 |
26.1 |
19.4 |
682 |
|
2/0 |
6/1 |
0.38 |
4.45 |
3.18 |
27.2 |
23.3 |
767 |
|
3/0 |
6/1 |
0.38 |
4.45 |
3.18 |
28.4 |
29.4 |
868 |
|
4/0 |
6/1 |
0.38 |
4.45 |
3.18 |
30.0 |
37.1 |
1002 |
|
266.8 |
18/1 |
0.38 |
4.45 |
3.18 |
31.1 |
30.3 |
1028 |
|
336.4 |
18/1 |
0.38 |
4.45 |
3.18 |
32.6 |
38.2 |
1179 |
|
3-Layer 35kV AAAC/XLPE/HDPE |
|||||||
|
48.69 |
7 |
0.38 |
4.45 |
3.18 |
22.6 |
7.83 |
441 |
|
77.47 |
7 |
0.38 |
4.45 |
3.18 |
24.2 |
12.4 |
523 |
|
123.3 |
7 |
0.38 |
4.45 |
3.18 |
26.4 |
18.9 |
644 |
|
155.4 |
7 |
0.38 |
4.45 |
3.18 |
27.5 |
23.8 |
718 |
|
195.7 |
7 |
0.38 |
4.45 |
3.18 |
28.9 |
30.0 |
811 |
|
246.9 |
7 |
0.38 |
4.45 |
3.18 |
30.4 |
37.8 |
922 |
|
312.8 |
19 |
0.38 |
4.45 |
3.18 |
32.1 |
46.5 |
1059 |
|
394.5 |
19 |
0.38 |
4.45 |
3.18 |
34.6 |
58.6 |
1238 |
|
465.4 |
19 |
0.38 |
4.45 |
3.18 |
35.6 |
69.2 |
1365 |
|
559.5 |
19 |
0.51 |
4.45 |
3.18 |
37.6 |
83.1 |
1547 |
|
652.4 |
19 |
0.51 |
4.45 |
3.18 |
39.0 |
97.0 |
1715 |
|
740.8 |
37 |
0.51 |
4.45 |
3.18 |
40.5 |
107 |
1874 |
|
927.2 |
37 |
0.51 |
4.45 |
3.18 |
43.4 |
135 |
2213 |
|
3-Layer 35kV AAC/XLPE/HDPE |
|||||||
|
1/0 |
7 |
0.38 |
4.45 |
3.18 |
25.3 |
7.96 |
590 |
|
2/0 |
7 |
0.38 |
4.45 |
3.18 |
26.2 |
9.99 |
653 |
|
3/0 |
7 |
0.38 |
4.45 |
3.18 |
27.3 |
12.15 |
731 |
|
4/0 |
7 |
0.38 |
4.45 |
3.18 |
28.7 |
15.30 |
829 |
|
266.8 |
19 |
0.38 |
4.45 |
3.18 |
30.2 |
19.89 |
946 |
|
336.4 |
19 |
0.38 |
4.45 |
3.18 |
32.1 |
24.57 |
1094 |
|
397.5 |
19 |
0.38 |
4.45 |
3.18 |
33.3 |
28.44 |
1210 |
|
477 |
19 |
0.38 |
4.45 |
3.18 |
35.1 |
33.30 |
1369 |
|
556.5 |
37 |
0.51 |
4.45 |
3.18 |
37.3 |
39.87 |
1538 |
|
636 |
37 |
0.51 |
4.45 |
3.18 |
38.8 |
45.36 |
1688 |
|
795 |
37 |
0.51 |
4.45 |
3.18 |
41.4 |
55.62 |
1980 |

Used for primary and secondary overhead distribution where limited space is available or desirable for rights of way.Installed as an uninsulated conductor, however, covering is effective in preventing direct shorts and instantaneous flashovers should tree limbs or other objects contact conductors in such close proximity.The resulting close-proximity configuration minimizes the amount of space and hardware required for line installation,particularly useful in congested areas such as alleyeays or tight corridors.